UPS Loads That Cause Problems

Q: What UPS inverter loads have the potential to cause problems with UPS operation?

A: The following load types either have very high inrush currents on startup or draw far more power than equivalent-sized loads:

  • Laser printers
  • Air conditioners and pumps
  • LED lighting (leading power factor)
  • Blade servers
  • Motor loads

Connecting these to a UPS causes it to go to bypass continuously with constant alarms, and during a battery discharge they will affect inverter operation. The two ways to handle them:

  1. Leave them off the UPS entirely (preferred for air conditioners and motors — see FAQ - Air Conditioner on UPS)
  2. Calculate the peak instantaneous power draw on startup and include this in UPS sizing — peak is often not on the device rating plate and must be obtained from the manufacturer